Mladenovic I, Weindl C (2008)
Publication Type: Conference contribution
Publication year: 2008
Edited Volumes: 2008 13th International Power Electronics and Motion Control Conference, EPE-PEMC 2008
Pages Range: 2045-2049
Conference Proceedings Title: 13th International Power Electronics and Motion Control Conference EPE-PEMC 2008
Event location: Poznan (Polen)
URI: http://www.eev.eei.uni-erlangen.de/Download/proceedings/2008-Poznan-Weindl-Mladenovic.pdf
DOI: 10.1109/EPEPEMC.2008.4635563
Monitoring the condition of electrical equipment insulation by means of partial discharge measurement and analysis is an effective diagnostic tool for the prediction of service failures. In this paper an accelerated aging system specialized for paper insulated lead covered (PILC) cables, with a highly sensitive and selective PD-detection/localization and tan(δ) measurement is presented. It facilitates the monitoring of the entire aging process and the later development of sophisticated diagnostic criteria based on the physical aging process. © 2008 IEEE.
APA:
Mladenovic, I., & Weindl, C. (2008). Determination of the Characteristic Life Time of Paper-insulated MV-Cables based on a Partial Discharge and tan(delta) Diagnosis. In 13th International Power Electronics and Motion Control Conference EPE-PEMC 2008 (pp. 2045-2049). Poznan (Polen).
MLA:
Mladenovic, Ivana, and Christian Weindl. "Determination of the Characteristic Life Time of Paper-insulated MV-Cables based on a Partial Discharge and tan(delta) Diagnosis." Proceedings of the 13th International Power Electronics and Motion Control Conference EPE-PEMC 2008, Poznan (Polen) 2008. 2045-2049.
BibTeX: Download